Use characteristics of 0.6/1kV PVC insulated overhead cable
2013-01-21
1) Rated voltage U0/U is 0.6/1kV.
2) Long-term allowable working temperature of cable conductor:
PVC, polyethylene insulation does not exceed 70 ℃.
XLPE insulation shall not exceed 90 ℃.
3) The laying temperature of the cable should not be lower than -20 ℃.
4) Allowable bending radius of cable:
Cable diameter (D) less than 25mm, should not be less than 4D.
Cable diameter (D) of 25mm and above, should not be less than 6D.